The SunGold Power 300 Amp DC Breaker Protects High-Current Battery Circuits and Gives You a Manual Disconnect
The SunGold Power 300 Amp DC Breaker is a two-pole molded case circuit breaker from SunGold's SG-C series. It protects DC circuits against overloads and short circuits, and it doubles as a manual disconnect between a battery bank and an inverter.
SunGold built it for larger battery banks and higher-power inverter systems. It suits installers wiring solar energy storage, off-grid or backup power systems who need a 300A protection point on the battery side.
SunGold Power 300 Amp DC Breaker Features
300A Rating up to 500V DC
The breaker is rated at 300A, with a rated operating voltage of DC12V to 500V.
25kA Short-Circuit Breaking Capacity
SunGold rates the short-circuit breaking capacity (Icu) at 25kA and the rated breaking capacity (Ics) at 20kA. A thermo-magnetic release handles both sustained overloads and short circuits.
Bidirectional for Charging and Discharging
The breaker supports battery charging and discharging, with the same overcurrent protection in either direction. Only the short-circuit breaking capacity changes with the wiring direction.
Manual Disconnect With Push to Trip
Marked ON and OFF positions let you isolate the battery or inverter for maintenance. A red button trips it by hand.
Panel Screw Mounting and Hexagon Screw Terminals
It mounts with panel screws and connects through hexagon screw terminals tightened to 5.0N.m. SunGold recommends 350 kcmil cable for the 300A rating.
Real-World Applications
Main battery disconnect. Place it between a large battery bank and an inverter.
Solar energy storage. Protect the energy storage side of a photovoltaic system.
Off-grid and backup power. Isolate the DC side of an off-grid or backup system for service.
Practical Comparison
SunGold Power 300 Amp DC Breaker Versus a Fuse
A fuse protects against overcurrent but has to be replaced once it blows. This breaker can be switched back on after a trip and also works as a disconnect.
SunGold Power 300 Amp DC Breaker Versus the 160A SG-C Model
Both share the same voltage rating, breaking capacity and frame size. The 300A model suits bigger battery banks, and SunGold pairs it with 350 kcmil cable instead of the 2/0 AWG cable it lists for 160A.
Buyer Guidance
Mounting and Operating Conditions
Mount it vertically with the arc chamber on top. SunGold prohibits horizontal and upside-down mounting and asks for arc flash clearance above it. It is rated for -10°C to +40°C ambient air, and its current correction coefficient falls to 0.85 at 40°C.
This May Be A Good Fit If
- Your battery circuit needs a 300A DC breaker
- Your system runs at 500V DC or less
- You want overload protection and a disconnect in one part
Common Questions
Which Terminals Connect to the Battery?
Connect the battery to the top LINE terminals and the inverter or load to the bottom LOAD terminals. This normal connection gives the full 25kA breaking capacity when the battery discharges.
How Do I Reset It After a Trip?
Push the handle down to OFF first, then push it up to switch it on. The handle can't be pushed up while the breaker is tripped.
Should a Professional Install It?
Yes. SunGold says installation must be carried out by specialists.
What's Included
- 1 x SunGold Power 300 Amp DC Breaker
Dependable Protection for Large Battery Banks
The SunGold Power 300 Amp DC Breaker gives a high-current battery circuit overload protection, short-circuit protection and a manual disconnect in one part. At Outbound Power, we help customers size breakers, cables and batteries for their inverter setups. If you have questions, our team is happy to help.
SunGold Power 300 Amp DC Breaker Specifications
|
| Electrical Ratings |
| Brand |
SunGold Power |
| Model |
SG-C300A |
| Series |
SG-C DC Molded Case Circuit Breaker (MCCB) |
| Rated Current |
300A |
| Poles |
2P |
| Rated Operating Voltage (Ue) |
DC12V~500V |
| Insulation Voltage (Ui) |
1000V |
| Rated Impulse Withstand Voltage (Uimp, 1.2/50) |
6kV |
| Rated Breaking Capacity (Ics) |
20kA |
| Rated Operating Short-Circuit Breaking Capacity (Icu) |
25kA |
| Icu by Direction (Normal Connection) |
25kA discharging, 15kA charging |
| Release Characteristic |
Thermo-magnetic, Curve (4-6In) |
| Use Category |
A |
| Current Direction |
Bidirectional (charging and discharging) |
| Mechanical and Installation |
| Electrical Life |
1000 cycles |
| Mechanical Life |
2000 cycles |
| Installation |
Panel screw installation, vertical only (arc chamber on top) |
| Terminal Connection Type |
Hexagon screw |
| Tightening Torque |
5.0N.m |
| Recommended Cable Size |
350 kcmil |
| Arcing Distance |
≤50mm |
| Dimensions (L x W x H) |
164 x 74 x 108 mm |
| Operating Conditions |
| Ambient Air Temperature |
-10°C to +40°C (24-hour average below +35°C) |
| Altitude |
Up to 2000m |
| Pollution Degree |
3 |
| Standards |
| Standard |
IEC/EN 60947-2 |
SunGold Power SG-C300A Data Sheet